Standard function blocks – Pilz PSS SB FT, Basic license User Manual

Page 158

Advertising
background image

6-114

Modular Block System: Burner Management

Standard Function Blocks

Block

Connection required

Reason

SB157

Perform

AND-operation

Flame fault

on all

ENBL from SB150

→

evaluation

FLAs (SB157)

Bit 0,

NEXT (SB158)

→

Detecting the step

BIT0 (SB157)

“Switch on ignition
transformer”

Bit 3,

NEXT (SB158)

→

Detecting the step

BIT3 (SB157)

“Pilot flame

established”
Pulse at

RDY (SB157)

→

Immediate further ignition

must set the step flag

NEXT attempt after a failure

of the previous step from
step “Switch on ignition
transformer”

STEP (SB152)

→

Burner start detection and

STEP (SB149, SB157)

resetting sequence

SB158

ENBL (SB152)

→

Valve seal when a

SyOK (SB158)

shutdown occurs

RUN (SB158)

→

For pilot flame

RUN (SB150)

monitoring

FLAI (SB158)

→

For pilot flame

MONI (SB150)

monitoring

Triggered pulse via neg. edge

Fault leads to a normal

from

ENBL (SB158)

shutdown (when

AuSt = 1

→

AND-connection before

with restart)

ERR (SB152)
or
Triggered pulse via neg. edge

Fault leads to a safety

from

ENBL (SB158)

shutdown

→

AND-connection before

CHAI (SB152)