Pilz PSS SB FT, Basic license User Manual

Page 147

Advertising
background image

Modular Block System: Burner Management

6-103

• Sequence for the set-up step

-

NEXT = 0: Set-up step not yet activated

° Enable

→

ENBL = 1

° Set-up step not active

→

RDY = 0

° Close main valve

→

VAV3 = 0

° Reset control enable

→

REGL = 0

° Main flame not established

→

RUN = 0

° Monitor main flame

→

FLAM = 1

-

NEXT, Bit 0 = 1:

Open main flame

° Enable

→

ENBL = 1

° Set-up step 1 active

→

RDY, Bit 0 = 1

° open main valve

→

VAV3 = 1

° Reset control enable

→

REGL = 0

° Main flame not established

→

RUN = 0

° Do not monitor main flame

→

FLAM = 0

-

NEXT, Bit 1 = 1:

Establish main flame

° Enable

→

ENBL = 1

° Set-up step 2 active

→

RDY, Bit 1 = 1

° Main valve open

→

VAV3 = 1

° Reset control enable

→

REGL = 0

° Main flame established

→

RUN = 1

° Monitor main flame

→

FLAM = 1

-

NEXT, Bit 2 = 1:

Set control enable

° Enable

→

ENBL = 1

° Set-up step 3 active

→

RDY, Bit 2 = 1