Output parameters, Function, Error messages – Pilz PSS SB FT, Basic license User Manual

Page 59

Advertising
background image

Modular Block System: Burner Management

6-15

Output parameters

ENBL: Enable flag bit

ENBL = 1: this function is fault-free
(refer also to the Programming guidelines)

Function:

Pilot and main flame monitoring from burner start-up to operating position,
through to burner switch-off.

Error messages

Any fault that is detected will be stored statically in the corresponding error
data word (SSNR) of DB015 (1st data block).

• Error messages in DB 015

- Bit00: Burner in operating position but no flame established

Remedy: Exit operating position (

RUN = 0),

and bring SB150 to the start position (

MONI = 1, F_S1 = 0,

F_S2 = 1, RUN = 0).

- Bit01: Burner not in the operating position, but the flame is established

Remedy: Bring SB150 to the start position (

MONI = 1, F_S1 =

0,

F_S2 = 1, RUN = 0).

- Bit02: Burner in the operating position and both flame monitor

contacts (

F_S1 and F_S2) have the value 1.

Remedy: Exit operating position (

RUN = 0), check flame

monitors' contacts and bring SB150 to the start position
(

MONI = 1, F_S1 = 0, F_S2 = 1, RUN = 0).

- Bit03: Burner in operating position and both flame monitor contacts

(

F_S1 and F_S2) have the value 0

Remedy: Exit operating position (

RUN = 0), check flame

monitor contacts and bring SB150 to the start position (

MONI

= 1,

F_S1 = 0, F_S2 = 1, RUN = 0).

- Bit04: Burner not in the operating position and both flame monitor

contacts (

F_S1 and F_S2) have the value 1

Remedy: Check flame monitor contacts and bring SB150 to the
start position(

MONI = 1, F_S1 = 0, F_S2 = 1, RUN = 0).

- Bit05: Burner not in the operating position and both flame monitor

contacts (

F_S1 and F_S2) have the value 0

Remedy: Check flame monitor contacts and bring SB150 to

the start position (

MONI = 1, F_S1 = 0, F_S2 = 1, RUN = 0).