Standard function blocks, Sb149: sequence control, Block header – Pilz PSS SB FT, Basic license User Manual

Page 45: Input parameters

Advertising
background image

Modular Block System: Burner Management

6-1

SB149: Sequence control

Block header

Input parameters

RDY:

Ready signal from the previous step
RDY = 1: ready signal is present

COND:

Global input for step enabling conditions for next step
COND = 1: all step enabling conditions fulfilled

• STEP:

Signals burner start-up for the duration of a cycle and
deactivates the step
STEP = 1: first cycle of burner start-up and deactivating the
step
STEP = 0: no burner start-up detected
This parameter must be assigned with the same operand used
for the output parameter

STEP from SB152 “Burner: Start and

operator elements” and for the input parameter

STEP of

SB157 “Ignition attempts” for the same burner.

W_BA:

Time base for step monitoring time (watchdog base)
Following values are valid:
0: 50 ms
1: 100 ms
2: 1 s
3: 10 s
4: 1 min

SB149

STEP

X - RDY
X - COND
X - STEP
B - W_BA

W - W_V

Z - W_T

B - D_BA

W - D_V

Z - D_T

NEXT - X

W_E - X

D_E - X