Modular Block System: Burner Management

SB151: Transient suppression

Version

Date

CRC

1.0

18.08.97

0F69

1.1

05.02.99

5710

Changes from Version 1.0 to Version 1.1
Internal start-up has been improved: Evaluation of the negative edge from
S1 in cases where SB 151 has not been called up in each cycle and
immediately after a cold start or reset, even though the block is required for
the application.

SB152: Burner: start and operator elements

Version

Date

CRC

1.0

09.12.97

2859

1.1

26.03.98

FF21

STOP

1.2

12.08.98

C491

Changes from Version 1.0 to Version 1.1

• Addition of input parameter

D_C.

- This parameter contains the number of cycles for the delayed enable of

SB 152 after the PSS has started-up. The delayed enable is required so
that the flame monitors can reach a defined position without a fault lock-
out occurring.

- The input parameter D_C replaces internally DL 1021 in DB 015.

• Addition of the output parameter

STEP.

- This parameter signals burner start-up for the duration of a cycle.

- The output parameter

STEP replaces internally Bit 0 from DW 1021 in

DB 015.

- This allows you to operate several work cycles (e.g. burners) on one

PSS.

• When starting after triggering the STOP-Signal, the signal to reset

the sequence (STEP) is set for the duration of one cycle.