Reset spurious acknowledgements, Spurious acknowledgement as valve opens – Pilz PSS SB FT, Basic license User Manual

Page 97

Advertising
background image

Modular Block System: Burner Management

6-53

Reset spurious acknowledgements

Spurious acknowledgement as valve opens

After a fault lock-out due to an incorrect acknowledgement,
a reset can only occur (with a positive edge at

RSET), if the

valve is closed (

Pos1 =1).

The valve positions OPEN/CLOSE are polled to the feedback
inputs

Pos1 and Pos2.

The inputs are polled for validity and the control time
OPEN

→

CLOSE and CLOSE

→

OPEN is monitored. If

faults occur, the

VAV output, together with the valve are

closed immediately and additionally

ENBL = 0 is set.

If the “1”-Signal remains off for a time shorter than the
block's set time, the

ENBLoutput is not set to "0".

Only after a “1” signal is off for a longer period will the
ENBL output be reset.