Modular Block System: Burner Management

Standard Function Blocks

L

M90.00

. main valve SB156

O

M90.01

. main valve SB159

=

A01.00

. main valve

• Resetting the sequence

To ensure the main valve seal when a shutdown occurs, the operand
used for the

ENBL from SB152 must be assigned to the input parameter

SyOK of SB159.
If the

ENBL of SB152 changes from “0” to “1” then SyOK of SB159 is

also set. The sequence block SB149 detects a positive edge and resets
the whole sequence as well as

NEXT from SB159.

Shutdown

If

SyOK = 0 or if an error is present (see error messages), a shutdown

occurs:

° No enable

ENBL = 0

° Set-up step not active

RDY = 0

° Close main valve

VAV3 = 0

° Reset control enable

REGL = 0

° Main flame not established

RUN = 0

° Monitor main flame

FLAM = 1

SB159

SB159

RUN

B - SSNR
B - NEXT
X - SyOK

ENBL - X

RDY - B

VAV3 - X - M

90.01

.main valve. SB159

REGL - X

RUN - X

FLAM - X