Modular Block System: Burner Management

6-7

• Deactivating a step

During burner start-up, the input parameter

STEP is set for one cycle.

The burner’s corresponding blocks evaluate this signal and reset the
sequence.

• Starting the initial step in a sequence:

The input parameter

RDY may not be assigned a communication flag

(M100.00 - M104.31) nor an input.
When using SB152 “Burner: Start and operator elements”, the output
parameter

STEP is set for the duration of a cycle, and the enable ENBL

is set. This parameter can be used to start the initial step.

Version 1: no conditions for the start of the initial step
The operand for the parameter

STEP can be assigned to the input

parameter

STEP of SB149 and the same operand can also be assigned

to the input parameter

RDY.

The input for the step enabling conditions

COND can be permanently

assigned with RLO1 (M110.01).

Example:

Version 2: conditions for the start of the initial step are present
The operand for the parameter

STEP may not be assigned directly to the

input parameter

RDY.

Example:

L

M 70.08

.Step_1

S

M 70.10

.RDY Step_1

SB149

STEP

M

70.08

.Step_1

- X - RDY

M

110.01 .RLO1

- X - COND

M

70.08

.Step_1

- X - STEP

B - W_BA

W - W_V

Z - W_T

B - D_BA

W - D_V

Z - D_T

NEXT - X

W_E - X

D_E - X