Modular Block System: Burner Management

6-87

Programming guidelines

•

ENBL

The negative edge of the enable

ENBL from SB158 must set a flag to “0”

for the duration of one PSS-cycle. This pulse flag must be supplied to the
AND-operation before the global input

ERR or to the AND-operation

before the global input

CHAI from SB152 “Burner: start and operator

elements”. The decision to use

ERR or CHAI depends on the user and

the respective standards regarding error reaction.

ERR: If an error occurs a controlled shutdown is carried out, when

AuSt = 1 with re-start

CHAI: If an error occurs a safety shutdown is carried out.

A programming example can be found in Chapter 8 under “Managing
enables”.

• Resetting the sequence

To ensure the valve seal when a shutdown occurs, the operand used for
the

ENBL from SB152 must be assigned to the input parameter SyOK

from SB158.
If the

ENBL from SB152 changes from 0 to 1, SyOK of SB158 is also set.

The SB149 “sequence control” detects the positive edge and resets the
whole sequence as well as

NEXT from SB158.

• Driving the safety valve VAV1

The situation could arise where the safety valve VAV1 is driven
simultaneously by SB156 “Tightness Control” and SB158 “Ignition”.

Solution: Assign different flags to the output parameter

VAV1 from

SB156 for VAV1 and the output parameter

VAV1 from SB158 for VAV1.

After calling up the SB, perform an OR-operation on both flags and drive
the corresponding peripheral output with the result of this logic operation.