6-14

Modular Block System: Burner Management

Standard Function Blocks

SB150: Flame monitoring

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB 001 ... KB 200
(further information about the SSNR can be found in the
sections “Administration data blocks DB015, DB016 and
SB017” and “Input parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

MONI:

MONI = 1: carries out flame monitoring:
When

RUN = 1: monitoring for “ flame established”

When

RUN = 0: monitoring for “flame not established”

The output parameter

FLAI from SB158 “Ignition” must be

supplied to this parameter when using SB150 for pilot flame
monitoring, and the output parameter

FLAM from SB159 “Run”

must be supplied to this parameter when using SB150 for main
flame monitoring.

F_S1:

Flame signal (N/O contact)
F_S1 = 1: flame established

F_S2:

Flame signal (N/C contact)
F_S2 = 1: flame not established

RUN:

The output parameter

RUN from SB158 “Ignition” must be

supplied to this parameter when using SB150 for pilot flame
monitoring, so that information about the status of the pilot
flame can be obtained. The output parameter

RUN from

SB159 “Run” must be supplied to the input parameter

RUN

from SB150 when using SB150 for main flame monitoring.
RUN = 1: monitoring for “flame established”

SB150

FLAME_M

B - SSNR
X - MONI
X - F_S1
X - F_S2
X - RUN

ENBL - X