Counting ignition attempts where time is exceeded, Successful ignition after first attempt failed – Pilz PSS SB FT, Basic license User Manual

Page 125

Advertising
background image

Modular Block System: Burner Management

6-81

Counting ignition attempts where time is exceeded

Setting input parameters

ITRY = 3: three ignition attempts

T_V = 10s: time monitoring

Successful ignition after first attempt failed

The monitoring time, within which the next ignition
attempt is permitted, will be started if

SyOK is no

longer present and at the same time

FLAs = 0, i.e.

no flame is established.
The acknowledgement (reset) and the new start-
command must be carried out before the
monitoring time cycle.

If the monitoring time

T_V has

elapsed, a third

RDY pulse is not

created.

The sequence must be started
from the beginning with the
initial step (reset+ start).

2nd ignition attempt

No 3rd attempt
because

T_V was

exceeded

When

BIT0 =1, it signals to the SB157 that the ignition

transformer was activated.
If a “1” signal is still present at the FLAs input by the 0-
1 signal change from

BIT3, it means that ignition was

successful and no more

RDY pulses will be created.

SB149 sequence continues.

1st ignition failure
(FLAs = 0)