Modular Block System: Burner Management

6-19

Timing diagrams

Signal cycle with an uninterrupted burner start-up or uninterrupted burner stop sequence

Monitoring for “Flame not established”

A “1”-Signal at the

MONI input and a “0”-Signal at the RUN input, F_S1 and

F_S2 are monitored for “0” and “1” respectively, i.e. for “flame not established”.
During the ignition process, the signals at

F_S1 and F_S2 must change, i.e.

SB 150 must change from detecting for “flame not established” to detecting
for “flame established”. During this switching time the

F_S1/F_S2-inputs

are not evaluated: they can have any status.

Monitoring for “flame established”

A “1”-Signal at the

MONI input and a “1”-

Signal at the

RUN-input means F_S1 is

monitored for “1” and

F_S2 for “0”, i.e. for

”flame not established”.

If the

MONI input is reset,

monitoring is deactivated and the
flame can be extinguished
without the block generating an
error message (

ENBL = 0).