BECKHOFF AX5805 Installation User Manual

Page 100

Advertising
background image

Error and diagnosis

98

AX5805

Error
index in
0xFA82

Error name

Description

Typical error
reaction time

0x5F02

FAULT_TMR2_INTERRUPT_C1

MC_Test: Timer2 has triggered an interrupt
on µC1. HighPrioISR was not called in time

0x5F03

FAULT_TMR2_INTERRUPT_C2

MC_Test: Timer2 has triggered an interrupt
on µC2. HighPrioISR was not called in time

0x5F04

FAULT_SWITCHOFF_TEST

MC_Test: the test of the switch-off channels
has failed

0x5F05

FAULT_NO_SYNC

No SYNC signal

0x5F06

FAULT_UNKNOWN_AXLE

The requested axis is unknown!

0x5F07

FAULT_FPGA_C2

The status of the FPGA is incorrect

0x5F08

FAULT_ANGLE_FORMAT_C1

The angles of C1 read-in have the wrong
format.

125 µs

0x5F09

FAULT_ANGLE_FORMAT_C2

The angles of C2 read-in have the wrong
format.

125 µs

0x5F0A

FAULT_SAFE_MAIN_STATE

Unknown state requested

0x5F0B

FAULT_STARTUP_FAILED

Error during start-up.

0x5F0C

FAULT_MOTION_DETECTION

Motion detection error

125 µs

0x6000

FAULT_PARAMETER_
FSOE_VENDOR_ID

Wrong Vendor ID transmitted

0x6001

FAULT_PARAMETER_
FSOE_MODULE_IDENT

Wrong Module ID transmitted

0x6002

FAULT_PARAMETER_FSOE_CRC

CRC of the AX5805 parameters do not fit to
the transmitted CRC (Please check
parameters and activate system manager
configuration and load safety configuration
to the EL69xx again)

Advertising