13

Commissioning

– contin ued –

CAN bus connection

The connection to the CANopen equipment is implemented via the CAN interface.

A D-subminiature plug connector in accordance with DIN 41652 must be used for the
connection. Use a multi-core flexible control cable as supply line.

Note that screened multi-core twisted-pair control cable is required as Bus line, e. g.
UNITRONIC

®

BUS CAN 2x 2 x...mm² or RE-2YCYV-fl 2x 2x ...mm².

UNITRONIC

®

is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.

C able leng th

N umber of pairs and conductor size [mm²]

125 m

2 x 2 x 0.34

250 m

2 x 2 x 0.5

335 m

2 x 2 x 0.75

500 m

available on demand (depends on bus configuration)

1000 m

1000 m

Note

The design and preparation of the data cable is an important factor for the
electromagnetic compatibility (EMC) of SPECTOR

control

.

Connection should therefore be carried out with special care
(see equipment specification of the display and operating panel HPG-200).