Can bus connection, Commissioning – Flowserve SPECTORcontrol User Manual
Page 13
13
– contin ued –
CAN bus connection
The connection to the CANopen equipment is implemented via the CAN interface.
A D-subminiature plug connector in accordance with DIN 41652 must be used for the
connection. Use a multi-core flexible control cable as supply line.
Note that screened multi-core twisted-pair control cable is required as Bus line, e. g.
UNITRONIC
®
BUS CAN 2x 2 x...mm² or RE-2YCYV-fl 2x 2x ...mm².
UNITRONIC
®
is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.
C able leng th
N umber of pairs and conductor size [mm²]
125 m
2 x 2 x 0.34
250 m
2 x 2 x 0.5
335 m
2 x 2 x 0.75
500 m
available on demand (depends on bus configuration)
1000 m
1000 m
Note
The design and preparation of the data cable is an important factor for the
electromagnetic compatibility (EMC) of SPECTOR
control
.
Connection should therefore be carried out with special care
(see equipment specification of the display and operating panel HPG-200).