Select standard curve, Select temperature coefficient, Menus of inputs/ outputs – Flowserve SPECTORcontrol User Manual
Page 34
34
– con tinued –
LRG 16-40 calibration
- con tinued -
S elect standard curve
1.
Click in the green input field of the menu
LRG 16-40 Calibration
2.
Select in the menu
Select standard curve
the
corresponding standard temperature curve. The
curves are applicable for various feedwater condi-
tioning agents with different basic conductivities.
For more information refer to the installation man-
ual of the equipment.
S elect temperature coefficient
1.
Click in the green input field of the menu
LRG 16-40 Calibration
2.
Select in the menu
Select temperature coef-
ficient
the corresponding gradient.
Note
With increasing pressure and temperature the conductivity is no longer a
linear function. Choose a suitable temperature compensation method.
Select standard curve
NaHO+H2O 260µS
NaHO+H2O 1080µS
NaHO+H2O 5400µS
NaHO+H2O 11200µS
Na3PO4+H2O 190µS
Na3PO4+H2O 1100µS
Select temp. coefficient
0
1.6 % / °C
1.7 % / °C
....
2.9 % / °C
3.0 % / °C