49

Controller Menu

– continued –

Pump setup

1.

Press button

Pump control

in the menu

2-pos. controller setup

.

2.

To adjust the pump press button

Pump

1...3

.

3.

Use the buttons to specify the mode of op-
eration (automatic / off / on) for each
pump. The lamp signal indicates that the
pump is operating.

4.

The total operating time of the pump is
highlighted in yellow.

5.

To delete the operating time press

.

Pump 1...3 setup

1.

Press button

Pump 1...3

in the menu

Pump Control

.

2.

The adjusted sensing element is indicated
in the green input field

Ready for opera-

tion

. Click in the input field to show all es-

tablished signals.

3.

Select the signal that indicates the re-
quired parameters. You will find more in-
formation on equipment setup in the menu
Digital Input.

4.

The adjusted signal receiver is indicated in
the green input field

Pump ON

. Click in the

input field to show all established signals.

5.

Select the signal that indicates the required parameters. You will find more informa-
tion on equipment setup in the menu Digital Output.

Pump
Setup

Logo

Pump 1

Pump 2

Pump 3

Ready

Ready

Ready

00000:00

00000:00

00000:00

Run time: hh:mm

Run time: hh:mm

Run time: hh:mm

Note

If several pumps are used and automatic operation is activated, first the
pump with the shortest operating time is selected, provided it is ready for
operation.

Pump 1

Setup

Logo

Pump ON

Ready for operation

NC

NC