Technical data – Fronius Agilo 75.0 User Manual

Page 111

Advertising
background image

109

EN

Technical data

Fronius Agilo
75.0-3

Input data

Output data

General data

Protection devices

MPP voltage range

460 - 820 V DC

Max. input voltage
(at 1000 W/m²/ -10 °C in an open circuit)

950 V DC

Max. input current

170,0 A

Max. short circuit current of the solar modules

255,0 A

Nominal output power (P

nom

)

75 kVA

Max. output power

75 kVA

Nominal grid voltage

3 ~ NPE 400 V / 230 V

Grid voltage tolerance

+10 / -5 %

1)

Nominal output current (three-phase)

112,4 A

Nominal frequency

50 - 60 Hz

1)

Total harmonic distortion

< 3 %

Power factor cos phi

1

0,8 - 1 ind./cap.

2)

Max. permitted mains impedance Z

max

at PCC

3)

66 mOhm

Max. feedback current

4)

0 A

5)

Starting current pulse

6)

0 A

5)

Max. output fault current per period

522 A / 2,47 ms

Maximum efficiency

97,3 %

Europ. efficiency

96,7 %

Overnight internal consumption

36 W

Cooling

Controlled forced-air ventilation

Degree of protection

IP 30

Dimensions l x w x h

1100 x 700 x 1884 mm

Weight

760 kg

Permitted ambient temperature
(at 95% rel. humidity)

- 20 °C - +50 °C

EMC emission class

A

Over-voltage category AC / DC

3 / 2

Degree of pollution

3

DC insulation measurement

Warning/shutdown

7)

at R

ISO

< 40 kOhm

Manifestation of DC overload

Operating point shift

power limitation

DC circuit breaker

Integrated

Advertising