Remedy

If the status code is displayed all the time: notify a Fronius-
trained service engineer

486
-

External NO contact is open

-

Optional measuring and monitoring relay has tripped

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

Close external NO contact;
check measuring and monitoring relay
If this status code keeps recurring, contact your system engi-
neer

487
Air inlet temperature sensor is faulty

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

Replace air inlet temperature sensor - notify a Fronius-trained
service engineer

488
AC measurement device is faulty

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

notify a Fronius-trained service engineer

490, 491
Internal communication error

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

notify a Fronius-trained service engineer

492
DC main switch is switched off

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

Switch on DC main switch

493
DC relay is faulty

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

notify a Fronius-trained service engineer

494
Grounding fault on the control board

Behaviour

The inverter is not feeding any energy into the grid.

Remedy

notify a Fronius-trained service engineer