Fronius Agilo 75.0 User Manual

Page 27

Advertising
background image

25

EN

Fan On

Cabinet fan in opera-
tion

Cabinet fan not
working

External ventilation /
air conditioning can
be activated

> 40 °C

max. internal tem-
perature >/= 40 °C

max. internal tem-
perature </= 30 °C

> 50 °C

max. internal tem-
perature >/= 50 °C

max. internal tem-
perature </= 40 °C

Sig. Rel.

NO/alarm contact
trips

Error confirmation at
the touch of a button
/ by Solar Net com-
mand

Status indicator / re-
lay contact switches

Running

Inverter feeding en-
ergy into the grid

Inverter not feeding
energy into the grid

Control of powered
non-return valve

Warning

Defined warning sta-
tus codes

Error confirmation at
the touch of a button
/ by Solar Net com-
mand

NO/alarm contact
activation, when cer-
tain warning status
codes occur at a
specific frequency
according to the 'Er-
ror-Counter' Service
menu

Error

Defined error status
codes

Error confirmation at
the touch of a button
/ by Solar Net com-
mand

NO/alarm contact
activation, when cer-
tain error status
codes occur at a
specific frequency
according to the 'Er-
ror-Counter' Service
menu

1)

Activation = the NC for the relay contact opens, the NO closes

2)

Deactivation = the NC for the relay contact closes, the NO opens

Function

Switch contact ac-
tivation criterion

1)

Switch contact de-
activation criteri-
on

2)

Description

Advertising