Fronius Agilo 75.0 User Manual

Page 92

Advertising
background image

90

Class 4 status
codes

Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.

Remedy

Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

IMPORTANT! Due to the low level of insolation early in the morning and in the evening,
the status code 307 (DC low) is routinely displayed at these times of day. This status code
does not indicate any kind of fault.
309
DC input voltage too high

Behaviour

Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.

Remedy

Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

321
Overcurrent (AC)

Behaviour

Short-term interruption while feeding energy into the grid due to
a grid fault or a power module fault
The inverter resumes with its startup routine.

Remedy

Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

322
Overtemperature on the air intake sensor

Behaviour

Permanent interruption while feeding energy into the grid

Remedy

Reduce the ambient temperature and ensure that a suitable hot
air extractor is installed if necessary
If this status code keeps recurring, contact your system engi-
neer

401
No communication with power stage set possible

Behaviour

The inverter will automatically attempt to connect again and, if
possible, will resume feeding energy into the grid

Remedy

If the status code is displayed all the time: notify a Fronius-
trained service engineer

406
Power module temperature sensor defective

Behaviour

The inverter is disconnected from the grid for safety reasons.