Description

Warning message is shown on the display

Remedy

If the status indicator appears all the time: notify a Fronius-
trained service engineer

551
Fuse for solar module grounding is faulty

Description

Warning message is shown on the display

Remedy

Replace fuse for solar module grounding - notify a Fronius-
trained service engineer; if this status code keeps recurring,
contact your system engineer

555
Circulating fan error

Description

Warning message is shown on the display

Remedy

If the status indicator appears all the time: notify a Fronius-
trained service engineer

558
Functional incompatibility (one or more PC boards in the inverter are not compatible with
each other, e.g. after a PC board has been replaced)

Description

Possible device errors or malfunctions on the inverter

Remedy

Update the inverter firmware using the Fronius Solar.update
software;
the latest inverter firmware is available from
http://www.fronius.com.
If the status indicator appears all the time: notify a Fronius-
trained service engineer

560
Power derating caused by overfrequency

Description

The status code is displayed from a grid frequency of 50.2 Hz
and above.
The inverter reduces the power along a 40%/Hz slope. The in-
verter switches off at a grid frequency of 51.5 Hz.
The status indicator is displayed until the inverter returns to nor-
mal operation.

Remedy

From a frequency of 50.2 Hz and above, the inverter tries to re-
connect to the grid.
The fault is rectified automatically as soon as the inverter re-
turns to normal operation.
If the status indicator appears all the time: notify a Fronius-
trained service engineer

597
External overvoltage protection has tripped (connected to the "IN1" NO/alarm contact ter-
minals)

Description

Warning message is shown on the display