NO/alarm terminals

S3 - 2 EXT

for connecting an external NO contact, e.g. to isolate the device from the
grid voltage using an AC contactor;
connected using bracket when delivered.

3 - 4

IN1
for connecting and evaluating a floating alarm contact

5 -6

IN2
for connecting and evaluating a floating alarm contact

7 - 8

IN3
for connecting and evaluating a floating alarm contact

The contacts must be potential-free.

Contact rating 24 V / 10 mA
Cable cross-section: 0.5 - 6 mm²
Tightening torque of terminals: 0.8 - 1.6 Nm

(7)

'Solar Net' LED
shows the current status of the Fronius Solar Net

(8)

Fuse F1 for switched-mode power supply, 4 A slow-blow