Device Status

For displaying the measured insulation resistance

Time

Setting time and date

IMPORTANT! The correct time and date is a prerequisite for the correct display of day and
year values and the day characteristic.

Status LT

The status display of the most recent inverter fault can be displayed.

IMPORTANT! Due to the low level of insolation early in the morning and in the evening,
the status codes 306 (Power low) and 307 (DC low) are displayed routinely at these times
of day. These status messages do not indicate any kind of fault.

-

Press the 'Enter' key to see the status of the power stage set and the most recent fault

-

Use the 'Up' and 'Down' keys to scroll through the list

-

Press the 'Back' key to close the status and fault list

Grid Status

The five most recent grid faults can be displayed:
-

Press the 'Enter' key to see the five most recent grid faults

-

Use the 'Up' and 'Down' keys to scroll through the list

-

Press the 'Back' key to close the grid fault display

Fan test

To check that the fan is working correctly

The fan test is started by pressing the 'Enter' key.
While the test is ongoing, its ' Progress' is shown on the display.

OK

Fan test successful

Fail

Fan is defective; the associated status code is displayed in 'NOW' view mode.

Version

Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)

Display area

Messwertanzeige
PV Iso. (Value in MOhm)

Unit

HH:MM, DDMMYYYY

Setting range

Time/date

Factory setting

-

Unit

-

Setting range

Start (Progress)

Factory setting

-