Fronius Agilo 75.0 User Manual

Page 77

Advertising
background image

75

EN

DC Mode

DC mode

FIX

Voltage value in V for fixed voltage operation

User

Voltage value in V for MPP User operation

Grid Monitoring:

GMTi

Start-up time of inverter in s

GMTr

Reconnection time in s following a grid fault

ULL

Mean grid voltage over 10 minutes in V.

LL Trip

Trip time for long-term voltage monitoring

Voltage Limits:

UIL max

Upper inner grid voltage in V

UIL min

Lower inner grid voltage in V

UOL max

Upper outer grid voltage limit value in V

UOL min

Lower outer grid voltage limit value in V

Frequency Limits:

FIL max

Upper inner grid frequency in Hz

FIL min

Lower inner grid frequency in Hz

FOL max

Upper outer grid frequency limit value in Hz

FOL min

Lower outer grid frequency limit value in Hz

LVFRT:

Status

Status of the LVFRT function (Low Voltage Fault Ride Through,
according to BDEW TR3 5.7)

DB min

Dead Band Value min.
Lower voltage limit as % for the reactive power feed

DB max

Dead Band Value max.
Upper voltage limit as % for the reactive power feed

k-Fac

Gradient showing how much reactive current is fed in as a func-
tion of voltage

P AC Reduction:

Max. P AC

Manual power reduction

GPIS

Softstart function

GFDPRv

Grid frequency-dependent power reduction in %/Hz

GFDPRr

Return to nominal output in %/s (following a grid frequency-in-
duced power reduction)