Class 3 status
codes

Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time.

The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.

301
Overcurrent (AC)

Behaviour

Short-term interruption while feeding energy into the grid due to
overcurrent in the alternating current circuit
The inverter resumes with its startup routine.

Remedy

Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

303
Power module overtemperature

Behaviour

Short-term interruption while feeding energy into the grid due to
overtemperature
The inverter resumes with its startup routine.

Remedy

Purge cooling air openings and heat sink if necessary;
fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

304
Internal temperature too high

Behaviour

Short-term interruption while feeding energy into the grid due to
overtemperature
The inverter resumes with its startup routine

Remedy

Purge cooling air openings and heat sink if necessary;
fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer

305
If the grid relay is closed, no energy is transferred to the grid

Behaviour

Permanent interruption while feeding energy into the grid

Remedy

If this status code keeps recurring, contact your system engi-
neer

307 (DC low)
DC input voltage too low for feeding energy into the grid

Behaviour

Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.