Troubleshooting, Blower does not operate – Greenheck IG / IGX (464104 IOM) (Pre-2009) User Manual

Page 61

Advertising
background image

61

Troubleshooting

Check Main Voltage

(See Blower Start-Up Step #1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary Fuses (FU6) or Secondary Fuses (FU7/8) Blown

(Replace Fuses)

Main Transformer (TR1) Defective

(Replace Transformer TR1)

24 VAC between

terminals R and X?

24 VAC between

terminals 8 and X?

Supply Fan Overload (ST1 OL) Tripped

(Reset and check motor amps, reference blower start-up #4)

24 VAC between

terminals 7 and X?

Damper Limit Switch (DL1) Holding

(Wait for actuator to open fully or adjust limit switch)

Damper Limit Switch Jumper Missing

(Install jumper, reference the units ladder diagram for terminals)

24 VAC between

terminals 6 and X?

Optional Exhaust Fan Interlocks (ST2-ST5) Open

(Correct/Replace)

Freeze Protection (FZ1) Tripped

(Reset)

24 VAC between

terminals G and X?

Supply Switch (S2) Off

(Turn Supply Switch S2 On)

Fire system contact (FSC) tripped

(Correct/Replace)

No

No

No

No

No

Yes

Yes

Yes

Yes

Note: At this time the supply contactor (ST1) should pull in passing

power to the supply motor and the blower should start.

Yes

Blower Does Not Operate

Broken Fan Belt

(Replace - Reference maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown Motor Fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

Troubleshooting