Troubleshooting motor overamps – Greenheck IG / IGX (464104 IOM) (Pre-2009) User Manual

Page 62

Advertising
background image

62

Troubleshooting

Motor Overamps

Air volume too high?

(Reference blower start-up step #5)

Adjust drives or increase external static pressure as

needed.

Motor horsepower too low?

Resize motor.

Motor voltage correct?

(Reference blower start-up step #1)

Provide proper power supply.

Blower rotation correct?

(Reference blower start-up step #2)

Reverse blower rotation.

Actual external static pressure

lower than design?

Adjust drives to reduce blower RPM.

No

No

Yes

Yes

Yes

Yes

No

Yes

No

No

Shorted windings in motor?

Replace motor.

Yes

Troubleshooting

Everything is working

properly, consult factory.

Yes

Advertising
This manual is related to the following products: