69

Internal control failure?

(ignition controller(s) LED on)

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

High limit switch (HLC#) open?

Discharge temperature was above high limit setting

Let cool then reset high limit.

Yes

Yes

No

Airflow fault?

(ignition controller LED

blinking once)

Pressure switch (PSL) failure

Repair or replace pressure switch (PSL)

Combustion blower (CM#) not functioning

Replace fusing (FU9), combustion blower or relay (CM#)

Yes

No

Ignition lockout?

(ignition controller LED

blinking three times)

Improper manifold pressure

Set high and low manifold pressure (refer to 4:1 mod. start-up)

Faulty spark rod or spark gap does not equal

1

8

in.

Replace spark rod or adjust gap to

1

8

in.

Yes

No

120 VAC between terminals

101 and 102?

...continued from previous

page

Secondary fuse (FU7) blown

Replace secondary fuse (FU7)

Main transformer (TR1) defective

Replace main transformer (TR1)

Secondary transformer (TR2) defective

Replace secondary transformer (TR2)

A200 defective

Replace A200

Furnace controller (FX) defective

Replace furnace controller (FX)

No

No

Yes

24 VAC between terminals

1 and 2 on the A200

No

Yes

24 VDC between terminals

3 and 4 on the A200

No

Yes

10 VDC between terminals

5 and 6 on the A200

Everything is working

properly, consult factory.

No

Yes

4:1 Modulating Furnace Will Not Light

Troubleshooting

Troubleshooting