Maintenance - Routine

Filters

Filter maintenance is generally limited to cleaning and
replacement.

If aluminum mesh filters are installed, they can be washed in
warm soapy water.

An adhesive spray can be added to aluminum mesh filters to
increase their efficiency.

If disposable filters are installed, they can be checked by
holding up to a light source. If light cannot pass through the
filter, it should be replaced.

IMPORTANT!

When reinstalling filters be sure to install

them with the airflow in the correct

direction. An airflow direction arrow is

located on the side of the filters.

IMPORTANT!

Replacement filters should be from the

same manufacturer and the same size as

the original filters provided with the unit.

Evaporative Coolers

The media should be periodically brushed lightly with a soft
bristle brush in an up and down motion while flushing with
water. This aids in reducing the amount of mineral build-up.

For large amounts of mineral build-up, clean or replace the
media and increase the water bleed-off or flush rate.

The cooling media has a useful life of 3 to 5 years depending
on the water quality and the bleed-off or flush rate.

Leaving Air

Entering Air

45°

15°

IMPORTANT!

Replacement media should be from the same

manufacturer and be the same size as the original

media provided with the unit.

IMPORTANT!

When reinstalling the evaporative media,

make sure that it is installed correctly.

Reference the drawing shown below.

Cooling Coils

Inspect the coil for signs of corrosion and/or leaks. Repair
any leaks as required.

Inspect the coil’s surface for foreign material. If the coil
surface needs cleaning, clean the coil from the leaving air-
side so that foreign material will be washed out of the coil
rather than pushed farther in.

Inspect and clean the drain pan to prevent the growth of
algae and other organisms.

IMPORTANT!

Be sure to read and follow the

manufacturer’s recommendations before

using any cleaning fluid.

WARNING!

Repair and replacement of the coil and

the connecting piping, valves, etc.,
should be performed by a qualified

individual.

Chilled Water Coils

Test the circulating fluid for sediment, corrosive products,
biological contaminants and make the necessary corrective
measures.

Maintain adequate fluid velocities and proper filtering of the
fluid.

If automatic air vents are not utilized, periodic venting of the
coil is recommended to remove accumulated air.

CAUTION!

Caution should be used to avoid injury

when venting the coil. High pressure

and/or high temperature fluids can cause

serious injuries.