Troubleshooting

Single Stage or 2:1 Staged Furnace Will Not Light

Internal control failure?

(ignition controller LED on)

Ignition controller (IC1) failed.

(Replace ignition controller)

High limit (HLC#) open?

Discharge temperature was above high limit setting.

Wait for high limit to cool and reset.

24 VAC across A and X?

Discharge air selector (TS2) improperly set or faulty

Adjust setting (see staged start-up) or replace sensor

Furnace stage one contact (SC1-1) defective (stage only)

Replace furnace stage one contact

24 VAC across 20 and X?

Supply starter relay (ST1) defective

Replace supply starter relay

Optional inlet air sensor contact (TS1) open

Adjust inlet air sensor setting (refer to blower start-up)

Yes

No

No

Yes

No

Yes

Yes

24 VAC across W1 and X?

Heat switch (S3) open or not wired

Close or replace heat switch

No

Yes

24 VAC across R and X?

Main disconnect (DS1) open or defective

Close, repair or replace

Fusing (FU6 and/or FU8) blown

Replace blown fusing

Main transformer (TR1) fault

Replace main transformer

No

Yes

Airflow fault?

(ignition controller LED

blinking once)

Combustion blower (CM1) not functioning

Replace fusing (FU9), combusting blower or relay (CM1)

Air proving switch (PS2) defective.

Replace air proving switch

Yes

No

Ignition lockout?

(ignition controller LED

blinking three times)

Improper manifold pressure

Set high and low manifold pressure (refer to start-up)

Faulty spark rod or spark gap does not equal

1

8

in.

Replace spark rod or adjust gap to

1

8

in.

Yes

No

Troubleshooting

Everything is working

properly, consult factory.