1 staged furnace will not light troubleshooting – Greenheck IG / IGX (464104 IOM) (Pre-2009) User Manual

Page 71

Advertising
background image

71

8:1 Staged Furnace Will Not Light

Troubleshooting

Internal control failure?

(ignition controller(s) LED on)

Ignition controller(s) (IC#) failed

Replace faulty ignition controller(s)

Yes

... continued from previous

page.

Does the combustion relay

(IR# or CR#) close?

Internal high limit tripped (temperature above set point)

Let temperatures cool

Internal inlet air sensor open

Adjust inlet air sensor setting (refer to 8:1 staged start-up)

Combustion relay (IR# or CR#) defective

Replace defective combustion relay (IR# or CR#)

No

Yes

Does the combustion blower

(CM#) run?

Combustion blower fuse (FU9) blown

Replace combustion blower fuse (FU9)

Combustion blower (CM#) defective

Replace defective combustion blower (CM#)

No

Yes

No

Ignition lockout?

(ignition controller LED

blinking three times)

No

Cycle power to the unit and

wait 30 seconds

Everything is working

properly, consult factory.

Improper manifold pressure

Set high and low manifold pressure (refer to 8:1 staged start-up)

Faulty spark rod or spark gap does not equal

1

8

in.

Replace spark rod or adjust gap to

1

8

in.

Yes

Does the combustion blower

stop after 30 seconds of

operation?

Airflow switch (PSH#) defective

Replace defective airflow switch

Airflow relay (PSR) defective

Replace defective airflow relay (PSR)

Yes

No

With the combustion blower

(CM#) on for at least 30

seconds, is there 24 VAC

across X and A1 or A2?

Furnace controller (FX) defective

Replace furnace controller (FX)

No

Yes

Troubleshooting