72

Troubleshooting

CAUTION!

Only proceed to steps two and three if step one does not correct the problem.

Step 2 Enter Program Mode

Press and hold the enter key for three
seconds to enter program mode. The
display will read “Pro” when program mode
is active.

Step 1 Adjust the Manual Supply Valve

Adjust the manual supply valve (refer to Water Wizard Start-Up Step #2). If the recommended water
pressure does not provide enough water, increase the pressure until the desired water supply is
achieved. If the recommended water pressure provides too much water, decrease the water pressure
until the desired water supply is achieved

Step 3 Adjust the On Time Factor

While in the program menu, use the up and
down keys to navigate through the menu
options until “ont” is displayed.

With “ont” displayed, press the enter key to
access the setting.

With the setting displayed, use the up and
down keys to adjust the setting as needed.

Increase the factor to increase the water
supply or decrease the factor to decrease
the water supply.

Press the enter key to save the new on
time factor and return to the program
menu.

Step 4 Exit Program Mode

After ten seconds of idle time the controller will automatically exit program mode.

NOTE!

If the water supply is too low, the media will

continuously appear dry.

NOTE!

Changing the on time factor by (1) will change

the water supply by approximately 3%.

NOTE!

If the water supply is too high, the media will be

saturated and excessive water will be draining

from the sump tank.

NOTE!

Some water drainage is desired to keep the media flushed, but it should be minimized to utilize the

Water Wizard.

IMPORTANT!

The enter key must be pressed to save the new

on time factor.