Technical Guide

VCM Controller

10

Controller Installation & Wiring

General

Correct wiring of the VCM controller is the most important factor in
the overall success of the controller installation process. In general most
VCM controllers are factory installed and wired at the AAON

®

factory.

It is also possible to purchase these controllers directly from WattMaster
Controls for installation in the field. Some of the following information
pertains to field wiring and may not apply to your installation since it
was pre-wired at the factory. However, in the unlikely event that trouble-
shooting of the controller is required, it is a good idea to be familiar
with the system wiring, no matter if it was factory or field wired.

Controller Mounting

When the controller is to be field mounted, it is important to mount the
controller in a location that is free from extreme high or low tempera-
tures, moisture dust and dirt. See Table 1 for a list of the required oper-
ating conditions for the VCM Controller and associated expansion
boards.

Be careful not to damage the electronic components when mounting
the controller. Remove the controller from its backplate. Mark the con-
trol enclosure base using the backplate as a template. Drill pilot holes in
the enclosure base and secure the backplate to it using sheet metal screws.
Do not allow metal shavings to fall onto the circuit board. Reattach the
controller to the backplate.

Important Wiring Considerations

The VCM controller and expansion boards must be connected to a 24
VAC power source of the proper size for the calculated VA load re-
quirements. All transformer sizing should be based on the VA rating
listed in Table 1.

Control

Device

V

oltage

VA

Load

O

perating

Tem

perature

O

perating

Hu

m

id

it

y

VCM Controller

Board

24VAC

60Hz

8

10

°

F to 149

°

F

90% RH

*N.C.

2 Slot Expansion

Base Board

24VAC

60Hz

10

10

°

F to 149

°

F

90% RH

*N.C.

4 Slot Expansion

Base Board

24VAC

60Hz

20

10

°

F to 149

°

F

90% RH

*N.C.

* Non-Condensing

Table 1: Voltage and Environment Requirements

Warning: When using a single transformer to power more

than one controller or expansion board, the correct
polarity must always be maintained between the
boards. Failure to observe correct polarity will
result in damage to the VCM controller and
expansion boards.

Please carefully read and apply the following information when wiring
the VCM controller or the VCM Expansion Boards. See Figure 5 for
VCM controller wiring diagram. See Figures 6, 7 and 8 for Expansion
Board Wiring.

1.

All wiring is to be in accordance with local and national

electrical codes and specifications.

2.

Minimum wire size for 24 VAC wiring should be 18 gauge.

3.

Minimum wire size for all sensors should be 24 gauge.

Some sensors require 2 conductor wire and some require 3

or 4 conductor wire.

4.

Be sure that all wiring connections are properly inserted

and tightened into the terminal blocks. Do not allow wire

strands to stick out and touch adjoining terminals which

could potentially cause a short circuit.

5.

When communication wiring is to be used to interconnect

VCM controllers together or to connect to other

communication devices, all wiring must be plenum rated,
minimum 18 gauge, 2 conductor, twisted pair with shield.
WattMaster can supply communication wire that meets this

specification and is color coded for the network or local

loop. Please consult your WattMaster distributor for

information. If desired, Belden #82760 or equivalent wire

may also be used.

6.

Before applying power to the VCM controller, be sure

to recheck all wiring connections and terminations
thoroughly.