Technical Guide

21

Supply Fan VFD Signal Or Zoning By-

pass Damper Actuator

The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a 0-
10 VDC
output. This signal output can be connected to the Supply Fan Variable
Frequency Drive to modulate the Supply Fan speed and control Duct
Static Pressure utilizing the Duct Static Pressure Sensor connected to
the VCM controller board. Alternatively it can be connected to a Zon-
ing Bypass Damper Actuator which will modulate the Zoning Bypass
Damper Actuator to control Duct Static Pressure utilizing the Duct Static
Pressure Sensor connected to the VCM controller board. A Duct Static

+

Supply Fan Variable Frequency Drive

(By Others)

_

VFD 0-10VDC Input

GND

Caution:

The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

OE331-21-VCM

VCM Controller Board

Bypass Damper Actuator

(Belimo Actuator Shown)

0-10 VDC

24 VAC Power Source

Sized For Actuator VA Load

GND

24 VAC

Y1 3

Y1 3

+ 2

+ 2

COM -

1

COM -

1

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

OE331-21-VCM

VCM Controller Board

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

Pressure Sensor must be connected in order for the VFD or Zoning
Bypass Damper Actuator to operate. See Figure 17 and Figure 18 for
detailed wiring.

Caution:

Variable Frequency Drive units can cause
large transient noise spikes which can cause
interference to be propagated on other
electronic equipment. Use shielded wire
wherever possible and route all sensor and
controller wiring away from the Variable
Frequency Drive and the HVAC Unit electrical

Figure 17: Supply Fan VFD Signal Wiring

Figure 18: Zoning Bypass Damper Signal Wiring