Figure 11: Supply Air and Return Air Temperature Sensor Wiring- Units Without MODGAS II or MHGRV II

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Mount In HVAC

Unit Supply

Air Duct

Mount In HVAC

Unit Return

Air Duct

OE331-21-VCM

VCM Controller Board

OE231

Supply Air Temperature Sensor

OE231

Return Air Temperature Sensor

Supply & Return Temperature Sensor

For applications that do not use either the AAON

®

MODGAS II or

MHGRV II boards, the Supply Air & Return Air Temperature Sensors
must be wired as shown in the Figure 11 for proper operation. The
Supply Air & Return Air Temperature Sensors are 10K Type III ther-
mistor sensors. The Supply Air Temperature Sensor should be mounted
in the unit discharge plenum or in the supply air duct. The Return Air
Temperature Sensor should be mounted in the return air duct. If the
system has a Zoning Bypass Damper installed, be sure the return air
sensor is located upstream of the bypass duct connection.

Note: If your AAON

®

HVAC unit uses the MODGAS II

Controller and/or the MHGRV II Controller, the
Supply Air Sensor must be wired to one of these
controllers and not to the VCM Controller.

Please see Figure 12 for Supply Air Temperature Sensor Wiring when
using the MODGAS II controller and/or the MHGRV II controller. The
Return Air Temperature Sensor always connects to the VCM controller
as shown in Figure 11