Input/Output Wiring Details

Binary Inputs Wiring

All Binary Inputs are to be wired as 24 VAC wet contact closures. Only
24 VAC power must be supplied to the OE356 Binary Input Board
through a Normally Open Contact closure in order for the signal to be
recognized by the controller. If a Dry Contact closure is used , it will
not work. See Figure 19 for detailed wiring.

OE352 or OE353 Expansion Base Board

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

R4

R3

R2

R1

YS101788

BIN 4

BIN 3

BIN 2

BIN 1

COM

TB1

OPTO2

R10

R12

4 DIG. IN MOD. I/O BD.

P2506-2

R8

R6

R5

P2506-2

OPTO1

74HC14N

PCF8574P

U2

C4

C3

U1

CX2

C2

C1

CX1

P1

R4

R3

R2

R1

YS101788

BIN 4

BIN 3

BIN 2

BIN 1

COM

TB1

OPTO2

R10

R12

4 DIG. IN MOD. I/O BD.

P2506-2

R8

R6

R5

P2506-2

OPTO1

74HC14N

PCF8574P

U2

C4

C3

U1

CX2

C2

C1

CX1

P1

OE356

-4

Binary

Input

Board

#1

OE356

-4

Binary

Input

Board

#2

Remote Forced Heating - N.O. Contact

Remote Forced Cooling - N.O. Contact

Exhaust Hood On - N.O. Contact

Dirty Filter - N.O. Contact

Proof Of Flow - N.O. Contact

Remote Forced Occupied - N.O. Contact

Smoke Detector - N.C. Contact

Remote Forced Dehumidification - N.O. Contact

COM

BIN4

BIN3

BIN2

BIN1

COM

BIN3

BIN4

BIN1

BIN2

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe
polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that
power to both the expansion boards and the controller are always powered together. Loss of power to the
expansion board will cause the controller to become inoperative until power is restored to the expansion board.

Figure 19: Binary Inputs Wiring

Warning: Do not apply any voltage greater than 24 VAC to

the Binary Input Expansion boards. Higher voltages
will damage the expansion Board and possibly
other components on the system.