VCM Controller

Technical Guide

27

Building Pressure Control

Output Wiring

The Building Pressure Control Output is a 0-10 VDC or 2-10 VDC
signal sent from the OE354, 4 Analog Input 1 Analog Output Expan-
sion Board. When using the output for Direct Building Pressure control
(output signal rises on a rise in building pressure), the output signal can
be connected to either a Variable Frequency Drive controlling an ex-
haust fan or to a damper actuator controlling an exhaust damper. When
used in this manner the output signal must be configured for Direct
Acting operation.

When using this output for Reverse Building Pressure Control (output
signal rises on a fall in building pressure), a damper actuator control-
ling an OA Damper would be used. When using the OA damper for
Reverse Building Pressure Control, the output signal must be config-
ured for Reverse Acting operation. A Building Pressure Sensor con-

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

OE354

-

4

Analog

Input

-

1

Analog

Output

Board

GND

AOUT1

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

PCF8591P

YS101784

D4

R4

D3

D1

D2

R2

R1

PHILIPS

T L

HA

AN

I D

CX1

U1

P1

+

Building Pressure Control

Exhaust Fan Variable Frequency Drive

(By Others)

_

0-10VDC or 2-10 VDC

(Configurable)

GND

The VFD Unit Must Be Configured For 0-10vdc Input. The
Input Resistance At The VFD Must Not Be Less Than 1000
Ohms When Measured At The VFD Terminals With All
Input Wires Removed.

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

OE352 or OE353 Expansion Base Board

Building Pressure Control

Damper Actuator

(By Others - Belimo Actuator Shown)

Wiring When Using Damper Actuator

For Building Pressure Control

Both Types Of Building Pressure Control

Devices Are Shown

Only One Type Of Building Pressure Control

Device May Be Used On Each HVAC Unit

Wiring When Using Exhaust Fan VFD

For Building Pressure Control

GND

24 VAC

Y1 3

Y1 3

+ 2

+ 2

COM -

1

COM -

1

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

nected to AIN4 on the OE354 Expansion board is used to sense and
control the signal to the Building Pressure Output. The OE258 Build-
ing Pressure Sensor must be connected in order for the Building Pres-
sure Output to operate correctly.

See Figure 24 for detailed wiring of the Building Pressure Control
Output Signal.

Caution:

Variable Frequency Drive units can cause large
transient noise spikes which can cause
interference to be propagated on other
electronic equipment. Use shielded wire
wherever possible and route all sensor and
controller wiring away from the Variable
Frequency Drive and the HVAC unit electrical
wiring.