Input/output wiring details, Technical guide vcm controller 28 co, Sensor wiring – Orion System VCM Controller User Manual

Page 28: Figure 25: co, Sensors are used to sense the current co, Sensor. see figure 25 for detailed wir- ing, Sensor and the expansion board

Advertising
background image

Technical Guide

VCM Controller

28

CO

2

Sensor Wiring

The OE255 or OE256 CO

2

Sensors are used to sense the current CO

2

level in the conditioned space. The pullup resistor PU3 must be re-
moved and the voltage jumper J03 must be in position (0-10 VDC posi-
tion ) on the OE354, 4 Analog Input 1 Analog Output Expansion Board
for proper operation of the CO

2

Sensor. See Figure 25 for detailed wir-

ing.

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

OE354

-

4

Analog

Input

-1

Analog

Output

Board

GND

AIN3

0-10 VDC Input

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

PCF8591P

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

OE255 or OE256

CO Sensor

(0-10VDC Signal)

2

1.

-

N

ot

Used

2.

-

N

ot

Used

4.

Relay

Common

5.

Relay

Norm

Closed

6.

4-20mA

Output

3.

Relay

Norm

Open

7.
Signal

Ground

8.

0-10V

Output

Pin

D

esignations

Pin

D

esignations

1.

AC+/DC+

2.

AC/GND

Pullup Resistor PU3 Must
Be Removed As Shown

Jumper J03 Must
Be In Place As Shown

OE352 or OE353 Expansion Base Board

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

Input/Output Wiring Details

Warning: It is extremely important to be certain that the

CO

2

Sensors “AC/GND” terminal is connected to

the GND terminal on the OE354 expansion board
and to the 24 VAC expansion base board power
source GND connection. The “AC+/DC+ ”
terminal on the CO

2

Sensor must be connected to

the 24 VAC power side of the 24 VAC power
source supplying power to the expansion base
board terminal as shown. Failure to observe the
correct polarity will result in damage to the HVAC
Unit Controller, CO

2

Sensor and the Expansion

Board.

Figure 25: CO

2

Sensor Wiring