Input/output wiring details, Figure 23: building pressure sensor wiring, Philips – Orion System VCM Controller User Manual

Page 26

Advertising
background image

Technical Guide

VCM Controller

26

Building Pressure Sensor Wiring

The OE258 Building Pressure Sensor must be wired as shown in the
illustration below for proper operation. There are 3 terminal connec-
tions on the OE258 Building Pressure Sensor. Connect the power side
of the 24 VAC power source to the terminal labeled “+ EXC” . Connect
the GND side of the 24 VAC power source to the terminal labeled “-
COM”. Connect the remaining terminal labeled “OUT” to AIN4 on the
OE354, 4 Analog Output 1 Analog Input Expansion Board terminal
block. See Figure 23 below for detailed wiring. The pullup resistor P4
on the expansion board must be removed and the voltage jumper J04

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

OE354

-

4

Analog

Input

Board

-

1

Analog

Output

Board

GND

AIN4

EXC

COM

OUT

0-5 VDC Input

HIGH

LOW

-

+

+

+

Tubing To Building
Pressure Sensing Location

Tubing To Atmospheric
Pressure Sensing Location

-

+

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

PCF8591P

YS101784

D4

R4

D3

D1

D2

R2

R1

PHILIPS

T L

HA

AN

I D

CX1

U1

P1

Pullup Resistor PU4 Must
Be Removed As Shown

Jumper J04 Must
Be Removed As Shown

OE352 or OE353 Expansion Base Board

OE258

Building Pressure Sensor

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

must also be removed as shown in the wiring diagram for the OE258
Building Pressure Sensor to operate correctly.

Warning: It is very important to be certain that all wiring

is correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result
in damage to the HVAC Unit Controller, Building
Pressure Sensor and the Expansion Board.

Figure 23: Building Pressure Sensor Wiring

Input/Output Wiring Details

Advertising