Appendix, Technical guide vcm controller 54, Oe265 rh sensor testing – Orion System VCM Controller User Manual

Page 54

Advertising
background image

Technical Guide

VCM Controller

54

Appendix

OE265-03 Relative Humidity Sensor

Testing Instructions:
Use the voltage column to check the Humidity Sensor while connected
to a powered expansion board. Read voltage with meter set on DC volts.
Place the “-”(minus) lead on terminal labeled GND and the “+” lead on

OE265 Relative Humidity Transmitters – Humidity vs. Voltage For 0-5 VDC Sensors

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

Humidity

Percentage

(RH)

Voltage

@

Input

(VDC)

0%

0.00

26%

1.30

52%

2.60

78%

3.90

2%

0.10

28%

1.40

54%

2.70

80%

4.00

4%

0.20

30%

1.50

56%

2.80

82%

4.10

6%

0.30

32%

1.60

58%

2.90

84%

4.20

8%

0.40

34%

1.70

60%

3.00

86%

4.30

10%

0.50

36%

1.80

62%

3.10

88%

4.40

12%

0.60

38%

1.90

64%

3.20

90%

4.50

14%

0.70

40%

2.00

66%

3.30

92%

4.60

16%

0.80

42%

2.10

68%

3.40

94%

4.70

18%

0.90

44%

2.20

70%

3.50

96%

4.80

20%

1.00

46%

2.30

72%

3.60

98%

4.90

22%

1.10

48%

2.40

74%

3.70

100%

5.00

24%

1.20

50%

2.50

76%

3.80

the AIN terminal that the Humidity sensor is connected to on the Ana-
log Input/Output Expansion Board.

OE265 RH Sensor Testing

The chart below is used to troubleshoot the OE265 Relative Humidity
Sensors.

Advertising