Expansion Board Installation & Wiring

Figure 7: Expansion Board Wiring Details For Binary Input, Analog Input and Analog Output Boards

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

R4

R3

R2

R1

YS101788

BIN 4

BIN 3

BIN 2

BIN 1

COM

TB1

OPTO2

R10

R12

4 DIG. IN MOD. I/O BD.

P2506-2

R8

R6

R5

P2506-2

OPTO1

74HC14N

PCF8574P

U2

C4

C3

U1

CX2

C2

C1

CX1

P1

R4

R3

R2

R1

YS101788

BIN 4

BIN 3

BIN 2

BIN 1

COM

TB1

OPTO2

R10

R12

4 DIG. IN MOD. I/O BD.

P2506-2

R8

R6

R5

P2506-2

OPTO1

74HC14N

PCF8574P

U2

C4

C3

U1

CX2

C2

C1

CX1

P1

OE356

-4

Binary

Input

Board

#

1

OE356

-4

Binary

Input

Board

#

2

OE355

-

4

Analog

Output

Board

Remote Forced Heating - N.O. Contact

Remote Forced Cooling - N.O. Contact

Hood On - N.O. Contact

Dirty Filter - N.O. Contact

Proof Of Flow - N.O. Contact

Remote Forced Occupied - N.O. Contact

+

COM

+

COM

VOUT (0-5V)

GND

VIN

VAC OR DC

GND

0-5V

0-10V OUTPUT

SIGNAL GROUND

+

-

AC/GND

AC+/DC+

LOW

HIGH

COM

COM

OUT

EXC

+

+

+

Smoke Detector - N.C. Contact

Remote Forced Dehumidification

N.O. Contact

AOUT2

AOUT4

GND

AOUT1

AOUT3

COM

BIN4

BIN3

BIN2

BIN1

COM

BIN3

BIN4

BIN1

BIN2

Plastic Tubing To Building
Pressure Sensing Locations

Building Pressure

Relief FAN VFD

Modular Cable

Connect To VCM Controller

Modular Cable

Connect To Next Expansion Board

(When Used)

24

V

A

C

GND

Orion - OE258 Building Pressure

Transducer

Orion - OE255 Room Mounted CO2 Sensor

Or

Orion - OE256 Return Air Mounted CO2 Sensor

Orion - OE265-13 Outdoor Air

Humidity Sensor

Orion OE265-11 Indoor Air

Humidity Sensor

Modulating Heating
(0 to 10 VDC Input)

Modulating Cooling

Or Digital Scroll Compressor

(1.5 to 5, 0 to 10 or 2 to 10 VDC Input)

Return Air Bypass

Damper Actuator

(0-10 VDC)

Return Air

Damper Actuator

(0-10 VDC)

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

When Copeland Scroll Compressor Is
Used Wire Per Copeland Digital Scroll
Wiring Detail

OE352 2 Slot Or OE353 - 4 Slot Expansion Board

As Required - OE353 Is Shown

10 VA Minimum Power Required For

Each OE352 - 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each OE353 - 4 Slot Expansion Base Board

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe
polarity will result in damage to one or more of the boards. Expansion Boards must be wired in such a way that
power to both the expansion boards and the controller are always powered together. Loss of power to the
expansion board will cause the controller to become inoperative until power is restored to the expansion board.

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

OE354

-

4

Analog

Input

-

1

Analog

Output

Board

AIN3

AOUT1

GND

AIN4

AIN1

AIN2

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

Y1

3

Y1

3

+

2

+

2

COM 1

COM 1

Wiring Considerations

The expansion base boards must be connected to 24 VAC as shown in
the wiring diagram below. Please see Table #1 for correct VA require-
ments to use when sizing the transformer(s) used for powering the ex-
pansion base boards.

Also please note that when wiring the OE356 - 4 Binary Input Expan-
sion Board(s), its contacts must be wired as wet contacts (connected to
24 VAC) not dry contacts as used with the OE357 - 4 Relay Expansion
Boards . See Figures 7 and 8 for complete wiring details.