Outdoor Air Humidity Sensor

When used with the VCM controller, the Outdoor Air Humidity Sensor
is connected to the system by wiring it to the AIN1 input on the OE354,
4 Analog Input 1 Analog Output Expansion board. It must be wired as
shown in Figure 20 for proper controller operation.

Jumpers Must Be Set as

Shown For Correct

O-5 VDC Operation

1 & 3 Are Off
2 & 4 Are On

Jumpers Must Be Set as

Shown For Normal

1, 2, 4, 5 & 6 Are Off

3 Is On

Operation Of Sensor

4-20

mA

Zero

Span

V

A

Co

rD

C

GND

0-5V

or

0-10V

4

4

4

5

5

6

6

ON

ON

ON

3

3

3

2

2

2

1

1

1

4

ON

3

2

1

24

V

A

C

GND

OE352 or OE353 Expansion Base Board

OE265-13

OA Humidity Sensor

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

0-5 VDC Input

OE354

-

4

Analog

Input

-

1

Analog

Output

Board

GND

AIN1

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

Pullup Resistor PU1 Must
Be Removed As Shown

Jumper J01 Must
Be Removed As Shown

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.
Failure to observe the correct polarity will
result in damage to the OA Humidity Sensor or
controller.

Figure 20: Outdoor Air Humidity Sensor Wiring