VCM Controller

Technical Guide

31

Return Air Bypass Wiring

The VCM controller can be configured for PAC or DPAC control
schemes. Both PAC and DPAC control schemes provide improved mois-
ture removal capabilities while utilizing internal space loads for reheat
by redirecting the Return Air around the Evaporator Coil instead of
through the coil. See the PAC and DPAC applications section of this
manual for complete operation details.

The PAC & DPAC control schemes both utilize a Return Air Bypass
Damper Actuator and a Return Air Damper Actuator to modulate the
Return Air and Return Air Bypass Dampers to control the amount of
air that is redirected around the Evaporator Coil.

The DPAC control scheme provides improved moisture removal ca-
pabilities and tighter temperature control than the PAC controls scheme
by combining Digital Compressor control in addition to Return Air
Bypass control.

See Figure 28 for detailed wiring of the Return Air Bypass and Return
Air Damper Actuators.

See Figure 16 for detailed wiring of the Digital Compressor.

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.
Failure to observe the correct polarity could
result in damage to the Damper Actuators or the
Analog Output expansion board.

Figure 28: Return Air Bypass Wiring

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Board

(When Used)

GND

AOUT4

AOUT3

0-10 VDC

0-10 VDC

GND

OE355

-

4

Analog

Output

Board

OE352 or OE353 Expansion Base Board

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

Return Air Bypass

Damper Actuator

(0-10 VDC)

Return Air

Damper Actuator

(0-10 VDC)

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

Y1

3

Y1

3

+

2

+

2

COM 1

COM 1