Input/output wiring details, Technical guide vcm controller 18, Economizer damper actuator – Orion System VCM Controller User Manual

Page 18

Advertising
background image

Technical Guide

VCM Controller

18

Figure 14: Economizer Damper Actuator Wiring

GND

AAON

Unit

Terminals

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

E

R

EC1

24 VAC Power Source

Sized For Actuator VA Load

24

V

A

C

GND

2-10 VDC

Output

Economizer Damper Actuator

(Belimo Actuator Shown)

Y1 3

Y1 3

+ 2

+ 2

COM -

1

COM -

1

OE331-21-VCM

VCM Controller Board

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

Economizer Damper Actuator

The Economizer Damper Actuator Signal voltage output is a 2-10 VDC
output. This signal output is used by the VCM controller to modulate
the Economizer Damper Actuator in order to control the amount of
Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor
Air Quality requirements. See Figure 14 for detailed wiring.

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.
Failure to observe the correct polarity will result in
damage to the actuator or VCM controller.

Input/Output Wiring Details