Input/output wiring details, Figure 27: modulating cooling device wiring, Warning – Orion System VCM Controller User Manual

Page 30

Advertising
background image

Technical Guide

VCM Controller

30

Modulating Cooling Device Wiring

The Modulating Cooling Device signal can be configured for either a
0-10 VDC, 2-10 VDC or 1.5-5.0 VDC output signal. The output signal
can also be configured for either Direct Acting or Reverse Acting op-
eration as required by your application. This signal output would nor-
mally be connected to a Modulating Chilled Water Valve or Digital
Compressor Controller.

See Figure 27 for detailed wiring of the Modulating Cooling Device
when using a Chilled Water Valve. When this output is used with a
Digital Compressor, the Suction Line Pressure Transducer must be wired

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Board

(When Used)

GND

AOUT2

+

Modulating Cooling Device

(By Others)

_

GND

OE355

-

4

Analog

Out

p

ut

Board

OE352 or OE353 Expansion Base Board

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

0-10 VDC, 2-10 VDC or 1.5-5.0 VDC

(Configurable)

The Modulating Cooling Device Used Must Be Designed
To Accept Either A 0-10 VDC, 2-10 VDC Or 1.5-5.0 VDC
Input. The AOUT1 Output Voltage Is User Configurable
For These Voltages. The Cooling Device Used Can Be A
Modulating Chilled Water Valve or A Digital Scroll
Compressor. If Using A Digital Scroll Compressor
Please See Digital Scroll Detailed

Information In

This Manual.

Wiring

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

to the Digital Compressor Controller instead of the VCM board and the
Modulating Cooling Output signal must be configured for a 1.5 to 5.0
VDC output signal. For Digital Compressor wiring details
see Figure 16.

Warning: It is very important to be certain that all wiring

is correct as shown in the wiring diagram
below. Failure to observe the correct polarity could
result in damage to the Modulating Cooling Device.

Figure 27: Modulating Cooling Device Wiring

Input/Output Wiring Details

Advertising