VCM Controller

32

Start-up & Commissioning

In order to have a trouble free start-up it is important to follow a few
simple procedures. Before applying power for the first time it is very
important to correctly address the controller and run through a few simple
checks.

Controller Addressing

All VCM controllers are equipped with address switches. If the VCM
controller is to operate as a stand alone system (not connected to any
other HVAC unit or VAV/Zone controllers) the controller address switch
should be set for address 1. When using the Modular Service Tool or
System Manager to program and configure the VCM controller you
would enter this address to communicate with the controller. When the
system is to be connected to other HVAC unit controllers on a commu-
nication loop, each controllers address switch must be set with a unique
address between 1 and 59. When the VCM controller will be used with
VAV/Zone controllers the VCM controller’s address switch must be set
as address 59, no exception. See Figure 29 for address switch setting
information. For detailed information regarding communication wiring
and connection for interconnected and networked systems, please see
the Orion System Installation & Troubleshooting Guide.

Power Wiring

One of the most important checks to make before powering up the sys-
tem for the first time, is to confirm proper voltage and transformer siz-
ing for the controller. Each VCM controller requires 8 VA of power
delivered to it at 24 VAC. Each 2 slot expansion board requires 10 VA

at 24 VAC and each 4 slot expansion board requires 20 VA at 24 VAC.
You may use separate transformers for each device (preferred) or power
several devices from a common transformer. If several devices are to be
powered from a single transformer correct polarity must be followed.

Warning: Observe Polarity! All boards must be wired with

GND-to-GND and 24 VAC-to-24 VAC. Failure to
observe polarity will result in damage to one or
more of the boards. Expansion Boards must be
wired in such a way that the Expansion Boards and
the VCM Controller are always powered together.
Loss of power to the Expansion Board will cause
it to become inoperative until power is restored to
the Expansion Board.

Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Confirm that
all sensors required for your system are mounted in the appropriate
location and wired into the correct terminals on the VCM controller. Be
sure any Expansion Boards connected to the VCM controller are also
correctly wired just as you did for the VCM controller.

After all the above wiring checks are complete, apply power to the
VCM controller and all expansion boards connected to it.

4

NETWORK

TOKEN

16

32

8

SW1

ADD

2

1

ADDRESS

V6

POWER

GND

24VAC

L1

D16

R6

C9

SC1

R1

1

U1

1

D13

C16

VR2

TB4

R27

C13

R10

VR1

C19

C18

R7

D10

R13

D12

C7

CX10

U10

CX12

U12

U14

CX14

PJ3

PJ2

PJ1

EXPANSION

PRESSURE
SENSOR

C17

D15

R26

C20

R25

R24

R22

U15

CX13

U13

C15

R19

R15

C14

D18

D17

PU1

PU2

PU3

PU4

PU5

PU7

D6

D7

D8

D9

D11

D14

C12

C10

0-5

VDC

0-1

VDC

JP1

C1

1

X2

GND

TB3

INPUTS

GND

GND

+VDC

AIN1

AIN2

AIN3

AIN4

AIN5

AOUT1

AOUT2

AIN7

RN5

D19

CX15

16
32

TOKEN

NETWORK

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

This Switch Should Be
In The OFF Position
As Shown

Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch Settings

Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication Loop
Wiring.

ADDRESS

ADD

ADDRESS

ADD

ADDRESS

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop And Be Between 1 and 59

Figure 29: VCM Controller Address Switch Setting

Advertising