Figure 26: modulating heating device wiring, Warning – Orion System VCM Controller User Manual

Page 29

Advertising
background image

VCM Controller

Technical Guide

29

Modulating Heating Device Wiring

The Modulating Heating Device signal can be configured for either a
0-10 VDC or 2-10 VDC output signal. The output signal can be config-
ured for either Direct Acting or Reverse Acting operation as required.

The Output signal is normally used to control a Modulating Hot Water
Valve, Modulating Steam Valve or for SCR Control of an Electric Heat-
ing Coil.

See Figure 26 for detailed wiring of the Modulating Heating Device.

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Board

(When Used)

GND

AOUT1

+

Modulating Heating Device

(By Others)

_

0-10 VDC or 2-10 VDC

(Configurable)

GND

The Modulating Heating Device Used Must Be Designed To
Accept Either a 0-10 Or a 2-10 VDC Input. The AOUT1
Output Voltage Is User Configurable For Either Voltage. The
Heating Device Used Can Be A Modulating Hot Water Valve,
Steam Valve Or SCR Controlled Electric Heating Coil.

OE355

-

4

Analog

Output

Board

OE352 or OE353 Expansion Base Board

WARNING!!

Observe Polarity! All boards must be wired with GND-to-
GND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered
together. Loss of power to the expansion board will cause
the controller to become inoperative until power is restored
to the expansion board.

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

Warning: It is very important to be certain that all wiring is

correct as shown in the wiring diagram below.
Failure to observe the correct polarity could
result in damage to the Modulating Heating Device
or the Analog Output expansion board.

Figure 26: Modulating Heating Device Wiring

Advertising