Speed and torque control output - 22 (0x16) – Yaskawa SI-EN3D User Manual

Page 22

Advertising
background image

u

Speed and Torque Control Output - 22 (0x16)

Output Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

22

0

0

Fault Reset

Run Fwd

1

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

2

4

Torque Reference/Torque Limit (Low Byte)

5

Torque Reference/Torque Limit (High Byte)

Name

Description

Run Fwd

Forward Run Command

0: Stop

1: Forward Run

Fault Reset

Fault Reset

(0 to 1 transition: Fault Reset)

Speed Reference

Speed Command

Sets drive speed reference.

Speed reference data: Frequency reference/2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF

Example: setting a reference of 4096 with a speed scale of 2:

Speed reference data = 4096/2

2

= 1024 = 0x0400 Hex

Unit depends on o1-03.

Torque Reference/Torque

Limit

Torque Reference/Torque Limit

Sets the Torque Reference/Torque Limit in units of 0.1%.

Sets the Torque Reference when using Torque Control (d5-01 = 1).

Sets the Torque Limit when using Speed Control (d5-01 = 0).

The Torque Reference and Torque Limit are disabled with F6-06 = 0.

u

Extended Speed and Torque Control Output - 23 (0x17)

Output Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

23

0

0

NetRef

NetCtrl

Fault Reset

Run Rev

Run Fwd

1

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

2

4

Torque Reference/Torque Limit (Low Byte)

5

Torque Reference/Torque Limit (High Byte)

Name

Description

Run Fwd

Forward Run Command

0: Stop

1: Forward Run

Run Rev

Reverse Run Command

0: Stop

1: Reverse Run

Fault Reset

Fault Reset

(0 to 1 transition: Fault Reset)

NetCtrl

Run command from Network

0: Depends on b1-02

1: Enables the run command from network

NetRef

Speed reference from Network

0: Depends on b1-01

1: Enables the speed reference from network

Speed Reference

Speed Command

Sets drive speed reference.

Speed reference data: Frequency reference/2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF

Example: setting a reference of 4096 with a speed scale of 2:

Speed reference data = 4096/2

2

= 1024 = 0x0400 Hex

Unit depends on o1-03.

8 Output Assemblies (Drive Consumes)

22

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual