Error Code

Description

0x22

Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done.

Writing “Enter” when drive is running.

Attempt to write data that is read only.

Attempt to write a parameter when drive is running.

During a CPF03 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.

0x23

Attempting to write during a drive undervoltage (Uv) event.

0x24

Attempting to write while the drive is storing data.

Note:

Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor

data using the MEMOBUS/Modbus message area.

u

Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 151 (0x97)

Input Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

151

0

0

Faulted

Alarm

Ready

Speed

Agree

Reset

REV

Running

ZSP

Running

1

ZSV

Multi-

Function

Photo-

coupler 2

Multi-

Function

Photo-

coupler 1

Multi-

Function

Digital

Output

LOCAL/

REMOTE

Uv

oPE

1

2

Output Frequency (Low Byte)

3

Output Frequency (High Byte)

2

4

Torque Actual (Low Byte)

5

Torque Actual (High Byte)

3

6

Current Actual (Low Byte)

7

Current Actual (High Byte)

Name

Description

Running

Running

0: Stop

1: Forward or Reverse Running

ZSP

Zero Speed

0: Running

1: Stop or DC Injection Braking

REV Running

Reverse Running

0: Not Reverse Running

1: Reverse Running

Reset

Reset

0: No Reset

1: Reset

Speed Agree

Speed Agree

0: No Speed Agree

1: Speed Actual at speed reference

Ready

Drive Ready

0: Not Ready

1: Ready

Alarm

Drive Alarm

0: No Drive Alarm

1: Alarm

Faulted

Drive Fault

0: No Drive Fault

1: Fault

OPE

OPE Fault

0: No oPE Fault

1: oPE

UV

Undervoltage

0: No Undervoltage

1: Undervoltage

LOCAL/REMOTE

Status of Run command from Network

0: Run command is not from network

1: Run command is from network

9 Input Assemblies (Drive Produces)

32

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual