Output Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

116

7

14

Analog Output 2 (Low Byte)

15

Analog Output 2 (High Byte)

8

16

Digital Outputs (Low Byte)

17

Digital Outputs (High Byte)

9

18

Reserved

19

Reserved

10

20-21

Programmable Bytes

Defined by F7-23

Default: Not Used

11

22-23

Programmable Bytes

Defined by F7-24

Default: Not Used

12

24-25

Programmable Bytes

Defined by F7-25

Default: Not Used

13

26-27

Programmable Bytes

Defined by F7-26

Default: Not Used

14

28-29

Programmable Bytes

Defined by F7-27

Default: Not Used

15

30-31

Programmable Bytes

Defined by F7-28

Default: Not Used

16

32-33

Programmable Bytes

Defined by F7-29

Default: Not Used

17

34-35

Programmable Bytes

Defined by F7-30

Default: Not Used

18

36-37

Programmable Bytes

Defined by F7-31

Default: Not Used

19

38-39

Programmable Bytes

Defined by F7-32

Default: Not Used

Name

Description

Run Fwd

Forward Run Command

0: Stop

1: Forward Run

Run Rev

Reverse Run Command

0: Stop

1: Reverse Run

Multi-Function Input 3

Terminal S3 Function Input

0: Terminal S3 Function (H1-03) OFF

1: Terminal S3 Function (H1-03) ON

Multi-Function Input 4

Terminal S4 Function Input

0: Terminal S4 Function (H1-04) OFF

1: Terminal S4 Function (H1-04) ON

Multi-Function Input 5

Terminal S5 Function Input

0: Terminal S5 Function (H1-05) OFF

1: Terminal S5 Function (H1-05) ON

Multi-Function Input 6

Terminal S6 Function Input

0: Terminal S6 Function (H1-06) OFF

1: Terminal S6 Function (H1-06) ON

Multi-Function Input 7

Terminal S7 Function Input

0: Terminal S7 Function (H1-07) OFF

1: Terminal S7 Function (H1-07) ON

Multi-Function Input 8

Terminal S8 Function Input

0: Terminal S8 Function (H1-08) OFF

1: Terminal S8 Function (H1-08) ON

8 Output Assemblies (Drive Consumes)

YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

27